Vacuum Circuit Breakers
and Feeder Protectors Products

15.5 KV 600 Amp Vacuum Circuit Breakers

Component

Application
Line Power Manufacturing’s Vacuum Circuit Breaker, 3 Phase, 15.5 KV Power Interrupting Device, Is Designed To Provide Protection For All Types Of Electric Feed Circuits Within Its Ratings.

Ratings (600 Amp Model)
Full Load Current: ……………………. 600 Amperes*
Maximum Voltage Rating: …………..15.5 KV
Rated Interrupting Capacity:……….12,500 Amperes Per IEEE Std. C37.60
BIL: ………………………………………. 95 KV
Loadbreak Rating …………………… 630 Amps, Per IEEE Std. C37.60

Features

  • Mechanically Interlocked Visible Disconnect.
  • Independent Bottle Wear Indicators.
  • Each Bottle Assembly Can Be Independently Adjusted For Proper ContactPressure To Ensure That Adequate Interrupting Capacities Are Met.
  • Optional Accessories
  • Load Side Grounding Of Visible Disconnect
  • Non-Isolated
  • Isolated
  • Shunt Trip
  • Undervoltage Release
  • Motor Operation
  • Key Interlocks

15.5 kV 600 Amp Vacuum Circuit Breaker Left-Hand Version

Component

Application
Line Power Manufacturing’s Vacuum Circuit Breaker, 3 Phase, 15.5 KV Power Interrupting Device, Is Designed To Provide Protection For All Types Of Electric Feed Circuits Within Its Ratings.

Ratings (600 Amp Model)
Continuous Current………………………… 600 Amperes*
Maximum Voltage…………………………… 15.5 KV
Symmetrical Interrupting Capacity………12,500 Amperes Per IEEE Std. C37.60
Lightning Impulse Withstand (BIL)………95 KV
Switching Current………………………….. 630 Amps, Per IEEE Std. C37.60

Features

  • Mechanically Interlocked Visible Disconnect.
  • Independent Bottle Wear Indicators.
  • Each Bottle Assembly Can Be Independently Adjusted For Proper Contact Pressure To Insure That Adequate Interrupting Capacities Are Met.
  • Optional Accessories
  • Load Side Grounding Of Visible Disconnect
  • Non-Isolated
  • Isolated
  • Shunt Trip
  • Undervoltage Release
  • Motor Operation
  • Key Interlocks

15.5 kV 1200 Amp Vacuum Circuit Breakers

Component

Application
Line Power Manufacturing’s Vacuum Circuit Breaker, 3 Phase, 15.5 KV Power Interrupting Device, Is Designed To Provide Protection For All Types Of Electric Feed Circuits Within Its Ratings.

Ratings (1200 Amp Model)
Continuous Current………………………..1200 Amperes
Maximum Voltage…………………………..15.5 KV
Symetrical Interrupting Capacity………18,000 Amperes
Lightning Impulse Withstand (BIL)……95 KV
Switching Current……………………….. 1200A

Features

  • Mechanically Interlocked Visible Disconnect.
  • Independent Bottle Wear Indicators.
  • Each Bottle Assembly Can Be Independently Adjusted For Proper Contact Pressure To Insure That Adequate Interrupting Capacities Are Met.
  • Optional Accessories
  • Load Side Grounding Of Visible Disconnect
  • Non-Isolated
  • Isolated
  • Shunt Trip
  • Undervoltage Release
  • Motor Operation
  • Key Interlocks

27 kV 600 Amp Vacuum Circuit Breakers

Component

Application
Line Power Manufacturing’s Vacuum Circuit Breaker, 3 Phase, 27 KV Power Interrupting Device, Is Designed To Provide Protection For All Types Of Electric Feed Circuits Within Its Ratings.

Ratings (600 Amp Model)
Continuous Current………………………. 600 Amperes*
Maximum Voltage …………………………………….27 KV
Symmetrical Interrupting Current …12,500 Amperes
Lightning Impulse Withstand (BIL) ……………125 KV
Switching Current…………………………. 600 Amperes

Features

  • Mechanically Interlocked Visible Disconnect.
  • Independent Bottle Wear Indicators.
  • Each Bottle Assembly Can Be Independently Adjusted For Proper Contact Pressure To Insure That Adequate Interrupting Capacities Are Met.
  • Optional Accessories
  • Load Side Grounding Of Visible Disconnect
  • Non-Isolated
  • Isolated
  • Shunt Trip
  • Undervoltage Release
  • Motor Operation
  • Key Interlocks

The Line Power Down Time Saver (DTS® II) Feeder Circuit Protector

Component

Line Power is proud to introduce the second generation of the Down Time Saver DTS® II for medium voltage feeder and motor protection.

The benchmark DTS® II design continues to serve the needs of our customers by saving them time and money. Traditional feeder circuit protection designs involve numbers components separately mounted in a fixed environment with numerous cables and wire connecting the circuits together. The more circuits, components and wires involved, the greater the probability of system failure, and time and money lost troubleshooting.

LP-2600 Circuit Protector

Component

General
The LP-2600 vacuum circuit protector is designed to replace 1000V, 600 amp mechanical circuit breakers now used by the mining industry. The accuracy and flexibility in the LP-2600 design provides the electrical engineer (or electrician) the means to monitor actual circuit load conditions and “fine tune” the circuit to reduce “nuisance tripping” while maintaining cable protection. The unit can also be used as a belt or pump controller – replacing the mechanical circuit breaker, control contactor and overcurrent relay. The modeling technique used by the LP-2600 provides dynamic protection for loads operating at their design limit.

 

Features

  • I2T Thermal-Overload Protection
  • Instantaneous Overcurrent Protection
  • Phase-Loss Protection
  • Stuck Vacuum Bottle Indication With Audible Alarm
  • Undervoltage Protection
  • Ground-Fault Protection
  • Ground-Monitoring Protection
  • Current Limiting Protection And Blown Fuse Detection
  • Temperature Sensing And Over Temperature Protection
  • Front-Panel Programming
  • Program-Change Lockout
  • Nonvolatile Memory For Programmed Values And Values At Trip
  • Digital Display Of: Load Current & Meter Values-At-Trip
  • -20°C To 40°C Operating Temperature
  • Optional Parameter-Selectable, Isolated
  • Analog Output

LP-2600-300 Circuit Protector

Component

General
The LP-2600-300 vacuum circuit protector is designed to replace 1000V, 300 amp mechanical circuit breakers now used by the mining industry. The accuracy and flexibility in the LP-2600-300 design provides the electrical engineer (or electrician) the means to monitor actual circuit load conditions and “fine tune” the circuit to reduce “nuisance tripping” while maintaining cable protection. The unit can also be used as a belt or pump controller – replacing the mechanical circuit breaker, control contactor and overcurrent relay. The modeling technique used by the LP-2600-300 provides dynamic protection for loads operating at their design limit.

Features

  • I2T Thermal-Overload Protection
  • Instantaneous Overcurrent Protection
  • Phase-Loss Protection
  • Stuck Vacuum Bottle Indication With Audible Alarm
  • Undervoltage Protection
  • Ground-Fault Protection
  • Ground-Monitoring Protection
  • Current Limiting Protection And Blown Fuse Detection
  • Temperature Sensing And Over Temperature Protection
  • Front-Panel Programming
  • Program-Change Lockout
  • Nonvolatile Memory For Programmed Values And Values At Trip
  • Digital Display Of: Load Current & Meter Values-At-Trip
  • -20°C To 40°C Operating Temperature
  • Optional Parameter-Selectable, Isolated
  • Analog Output